14 changes: 14 additions & 0 deletions Models/IoTesting/FatLiveValueObservation.cs
Original file line number Diff line number Diff line change
@@ -0,0 +1,14 @@
namespace ArIED61850Tester.Models.IoTesting;

/// <summary>
/// Generic live IEC 61850 value image used by FAT v2. Unlike the legacy digital
/// observation model, the raw value is intentionally not normalized to bool.
/// </summary>
public sealed record FatLiveValueObservation(
string RawValue,
DateTimeOffset CapturedAt,
DateTimeOffset? IedTimestamp,
string Quality,
string AcquisitionSource,
long Sequence,
long ConnectionGeneration);
170 changes: 170 additions & 0 deletions Models/IoTesting/FatVerificationModels.cs
Original file line number Diff line number Diff line change
@@ -0,0 +1,170 @@
using System.Text.Json.Serialization;

namespace ArIED61850Tester.Models.IoTesting;

/// <summary>
/// FAT v2 treats every static DataSet member as verification scope by default.
/// Inclusion is an operator decision and must never be changed by acquisition state.
/// </summary>
public enum FatSignalDisposition
{
Included,
ExcludedByOperator
}

public enum FatSignalKind
{
Discrete,
Analog,
Other
}

public enum FatCaptureMode
{
AutomaticTransition,
OperatorSnapshot
}

public enum FatValueSlot
{
Value1,
Value2
}

public enum FatEvidenceCaptureKind
{
AutomaticTransition,
OperatorSnapshot
}

public sealed record FatValueEvidence(
Guid EvidenceId,
FatValueSlot Slot,
FatEvidenceCaptureKind CaptureKind,
string RawValue,
DateTimeOffset CapturedAt,
DateTimeOffset? IedTimestamp,
string Quality,
string AcquisitionSource,
long Sequence,
long ConnectionGeneration);

/// <summary>
/// One FAT row. Identity follows static DataSet membership, not only the resolved runtime
/// reference, so the same IEC object may legitimately appear in more than one DataSet.
/// </summary>
public sealed class FatVerificationSignal
{
[JsonInclude]
public FatSignalDisposition Disposition { get; private set; } = FatSignalDisposition.Included;

public required string SignalId { get; init; }
public required string IedName { get; init; }
public string AccessPointName { get; init; } = string.Empty;
public required string DataSetReference { get; init; }
public int DataSetMemberIndex { get; init; }
public required string StaticMemberReference { get; init; }
public required string RuntimeReference { get; init; }
public string SignalName { get; init; } = string.Empty;
public string FunctionalConstraint { get; init; } = string.Empty;
public string DataType { get; init; } = string.Empty;
public FatSignalKind SignalKind { get; init; } = FatSignalKind.Other;
public FatCaptureMode CaptureMode { get; init; } = FatCaptureMode.OperatorSnapshot;

[JsonInclude]
public FatValueEvidence? Value1Evidence { get; private set; }

[JsonInclude]
public FatValueEvidence? Value2Evidence { get; private set; }

[JsonIgnore]
public bool IsIncludedInFat => Disposition == FatSignalDisposition.Included;

[JsonIgnore]
public bool HasCompleteEvidence => Value1Evidence is not null && Value2Evidence is not null;

/// <summary>
/// Explicit operator action. Removing a row never destroys evidence or source identity.
/// </summary>
public void RemoveFromFat() => Disposition = FatSignalDisposition.ExcludedByOperator;

/// <summary>
/// Explicit operator action. Restoring a row returns the same row and evidence to scope.
/// </summary>
public void RestoreToFat() => Disposition = FatSignalDisposition.Included;

public void SetCurrentEvidence(FatValueEvidence evidence)
{
ArgumentNullException.ThrowIfNull(evidence);
if (evidence.Slot == FatValueSlot.Value1)
Value1Evidence = evidence;
else
Value2Evidence = evidence;
}
}

public sealed class FatVerificationProject
{
public string ProjectId { get; init; } = Guid.NewGuid().ToString("N");
public List<FatVerificationSignal> Signals { get; init; } = new();

[JsonIgnore]
public IReadOnlyList<FatVerificationSignal> IncludedSignals =>
Signals.Where(signal => signal.IsIncludedInFat).ToArray();

[JsonIgnore]
public IReadOnlyList<FatVerificationSignal> RemovedSignals =>
Signals.Where(signal => !signal.IsIncludedInFat).ToArray();

public bool RemoveSignal(string signalId)
{
var signal = FindSignal(signalId);
if (signal is null)
return false;
signal.RemoveFromFat();
return true;
}

public bool RestoreSignal(string signalId)
{
var signal = FindSignal(signalId);
if (signal is null)
return false;
signal.RestoreToFat();
return true;
}

public int RestoreSignals(IEnumerable<string> signalIds)
{
ArgumentNullException.ThrowIfNull(signalIds);
var requested = signalIds.ToHashSet(StringComparer.OrdinalIgnoreCase);
var restored = 0;
foreach (var signal in Signals)
{
if (!requested.Contains(signal.SignalId) || signal.IsIncludedInFat)
continue;
signal.RestoreToFat();
restored++;
}
return restored;
}

public int RestoreAllSignals()
{
var restored = 0;
foreach (var signal in Signals.Where(signal => !signal.IsIncludedInFat))
{
signal.RestoreToFat();
restored++;
}
return restored;
}

private FatVerificationSignal? FindSignal(string signalId)
{
if (string.IsNullOrWhiteSpace(signalId))
return null;
return Signals.FirstOrDefault(signal =>
signal.SignalId.Equals(signalId, StringComparison.OrdinalIgnoreCase));
}
}
155 changes: 155 additions & 0 deletions Services/IoTesting/FatDataSetSignalProjectionService.cs
Original file line number Diff line number Diff line change
@@ -0,0 +1,155 @@
using System.Globalization;
using System.Security.Cryptography;
using System.Text;
using AR.Iec61850.Discovery;
using AR.Iec61850.Scl.Workspace;
using ArIED61850Tester.Models.IoTesting;

namespace ArIED61850Tester.Services.IoTesting;

/// <summary>
/// ARSAS FAT v2 consumer adapter over ARIEC-owned static DataSet authority.
///
/// This service does not parse SCL, infer FCDA semantics, or deduplicate by runtime object
/// reference. ARIEC remains the authority for mandatory DataSet descriptors; ARSAS creates
/// exactly one FAT row per static DataSet membership.
/// </summary>
public static class FatDataSetSignalProjectionService
{
public static IReadOnlyList<FatVerificationSignal> Project(SclIedWorkspace workspace)
{
ArgumentNullException.ThrowIfNull(workspace);
ArgumentNullException.ThrowIfNull(workspace.DesignModel);
return Project(workspace.IedName, workspace.AccessPointName, workspace.DesignModel);
}

public static IReadOnlyList<FatVerificationSignal> Project(
string iedName,
string accessPointName,
LiveIedModelDiscoveryDocument model)
{
ArgumentException.ThrowIfNullOrWhiteSpace(iedName);
ArgumentNullException.ThrowIfNull(model);

var descriptors = Iec61850DataSetSignalInventoryProjection.GetMandatorySignals(model);
var rows = descriptors
.SelectMany(descriptor => descriptor.DataSetMemberships.Select(membership =>
CreateRow(iedName.Trim(), accessPointName?.Trim() ?? string.Empty, descriptor, membership)))
.OrderBy(row => row.DataSetReference, StringComparer.OrdinalIgnoreCase)
.ThenBy(row => row.DataSetMemberIndex)
.ThenBy(row => row.StaticMemberReference, StringComparer.OrdinalIgnoreCase)
.ToArray();

var staticMemberCount = model.DataSets.Sum(dataSet => dataSet.Members.Count);
if (rows.Length != staticMemberCount)
{
throw new InvalidDataException(
$"ARIEC static DataSet projection returned {rows.Length} FAT membership row(s), " +
$"but the SCL design model contains {staticMemberCount}. FAT import refuses to silently drop or invent DataSet members.");
}

var duplicateIdentity = rows
.GroupBy(row => row.SignalId, StringComparer.OrdinalIgnoreCase)
.FirstOrDefault(group => group.Count() > 1);
if (duplicateIdentity is not null)
{
throw new InvalidDataException(
$"Static DataSet membership identity is not unique for FAT signal '{duplicateIdentity.Key}'.");
}

return rows;
}

private static FatVerificationSignal CreateRow(
string iedName,
string accessPointName,
Iec61850SignalDescriptor descriptor,
Iec61850SignalDataSetMembership membership)
{
var staticReference = FirstNonEmpty(
membership.CanonicalMemberReference,
membership.OriginalMemberReference,
descriptor.DesignReference,
descriptor.ObservedReference,
descriptor.PrimaryValueReference);
var runtimeReference = FirstNonEmpty(
descriptor.PrimaryValueReference,
descriptor.DesignReference,
descriptor.ObservedReference,
staticReference);
var dataType = FirstNonEmpty(descriptor.MmsType, descriptor.SclBType, "Unknown");
var signalKind = Classify(descriptor.FunctionalConstraint, dataType);

return new FatVerificationSignal
{
SignalId = BuildSignalId(
iedName,
accessPointName,
membership.DataSetReference,
membership.MemberIndex,
staticReference),
IedName = iedName,
AccessPointName = accessPointName,
DataSetReference = membership.DataSetReference,
DataSetMemberIndex = membership.MemberIndex,
StaticMemberReference = staticReference,
RuntimeReference = runtimeReference,
SignalName = FirstNonEmpty(descriptor.DataObject, descriptor.DataAttributePath, staticReference),
FunctionalConstraint = descriptor.FunctionalConstraint,
DataType = dataType,
SignalKind = signalKind,
CaptureMode = signalKind == FatSignalKind.Discrete
? FatCaptureMode.AutomaticTransition
: FatCaptureMode.OperatorSnapshot
};
}

internal static FatSignalKind Classify(string? functionalConstraint, string? dataType)
{
var fc = (functionalConstraint ?? string.Empty).Trim().ToUpperInvariant();
var type = (dataType ?? string.Empty).Trim().ToUpperInvariant();

if (fc == "MX" ||
type.Contains("FLOAT", StringComparison.Ordinal) ||
type.Contains("DOUBLE", StringComparison.Ordinal) ||
type.Contains("ANALOG", StringComparison.Ordinal))
{
return FatSignalKind.Analog;
}

if (type.Contains("BOOLEAN", StringComparison.Ordinal) ||
type.Contains("BOOL", StringComparison.Ordinal) ||
type.Contains("DBPOS", StringComparison.Ordinal) ||
type.Contains("DOUBLE-POINT", StringComparison.Ordinal) ||
type.Contains("DOUBLE POINT", StringComparison.Ordinal))
{
return FatSignalKind.Discrete;
}

// ST is intentionally not assumed to be boolean by itself. Enumerated/integer ST
// values need an explicit discrete semantic before automatic two-state capture.
return FatSignalKind.Other;
}

private static string BuildSignalId(
string iedName,
string accessPointName,
string dataSetReference,
int memberIndex,
string staticReference)
{
var identity = string.Join("|", new[]
{
iedName.Trim(),
accessPointName.Trim(),
dataSetReference.Trim(),
memberIndex.ToString(CultureInfo.InvariantCulture),
staticReference.Trim()
});
var bytes = SHA256.HashData(Encoding.UTF8.GetBytes(identity));
return "fat-" + Convert.ToHexString(bytes).ToLowerInvariant();
}

private static string FirstNonEmpty(params string?[] values)
=> values.FirstOrDefault(value => !string.IsNullOrWhiteSpace(value))?.Trim() ?? string.Empty;
}
57 changes: 57 additions & 0 deletions Services/IoTesting/FatOperatorSnapshotCaptureService.cs
Original file line number Diff line number Diff line change
@@ -0,0 +1,57 @@
using ArIED61850Tester.Models.IoTesting;

namespace ArIED61850Tester.Services.IoTesting;

/// <summary>
/// Captures the value currently read from the IED when the FAT operator explicitly
/// confirms Value 1 or Value 2. No injected/reference value or tolerance exists here;
/// this first public milestone proves trustworthy reading capture only.
/// </summary>
public static class FatOperatorSnapshotCaptureService
{
public static FatValueEvidence Capture(
FatVerificationSignal signal,
FatValueSlot slot,
FatLiveValueObservation observation)
{
ArgumentNullException.ThrowIfNull(signal);
ArgumentNullException.ThrowIfNull(observation);

if (!signal.IsIncludedInFat)
{
throw new InvalidOperationException(
$"FAT signal '{signal.SignalName}' is removed from the active FAT scope and cannot capture evidence until it is restored.");
}

if (signal.CaptureMode != FatCaptureMode.OperatorSnapshot)
{
throw new InvalidOperationException(
$"FAT signal '{signal.SignalName}' uses {signal.CaptureMode} capture and cannot be manually snapshotted.");
}

if (string.IsNullOrWhiteSpace(observation.RawValue) ||
observation.RawValue.Trim() is "-" or "—")
{
throw new InvalidOperationException(
$"FAT signal '{signal.SignalName}' does not have a readable live value to capture.");
}

var evidence = new FatValueEvidence(
Guid.NewGuid(),
slot,
FatEvidenceCaptureKind.OperatorSnapshot,
observation.RawValue.Trim(),
observation.CapturedAt,
observation.IedTimestamp,
string.IsNullOrWhiteSpace(observation.Quality) ? "Unknown" : observation.Quality.Trim(),
string.IsNullOrWhiteSpace(observation.AcquisitionSource) ? "Unknown" : observation.AcquisitionSource.Trim(),
observation.Sequence,
observation.ConnectionGeneration);

// This intentionally replaces only the current Value 1/Value 2 evidence pointer.
// The session/journal adapter remains responsible for appending every capture to
// immutable historical evidence before this service is wired into the public UI.
signal.SetCurrentEvidence(evidence);
return evidence;
}
}
Loading
Loading